You are viewing a free preview of this lesson.
Subscribe to unlock all 12 lessons in this course and every other course on LearningBro.
Spec mapping: OCR H556 Module 4.2 — Energy, power and resistance (electrical power P=IV and its derived forms P=I2R and P=V2/R; energy transferred W=Pt=VIt; the kilowatt-hour as a domestic energy unit; application to fuses, heating elements and transmission losses). Refer to the official OCR H556 specification document for exact wording.
Whenever charge moves through a potential difference, energy is transferred. A resistor turns that energy into heat; a lamp turns it into heat plus light; a motor turns it into mechanical work; a charger turns it into chemical potential energy in a battery. The rate of that energy transfer is the electrical power, and one equation — P=IV — connects every scenario.
This lesson derives the three equivalent forms P=IV=I2R=V2/R, computes total energy via W=Pt, and brings the formula to bear on practical questions every OCR candidate should be able to solve cold: fuse selection, transmission-line losses, kWh-to-joule conversion, and the heating element design that closes the loop with resistivity (lesson 7). By the end you should treat any "power" question as a one-line substitution, not a guessing game.
Power is energy per unit time:
P=tW
For electrical energy delivered to a component, energy per unit charge is the pd (V=W/Q) and charge per unit time is the current (I=Q/t). Multiplying:
P=tW=tVQ=V×tQ=VI
This gives the foundational electrical-power equation:
P=IV
| Quantity | Symbol | SI unit |
|---|---|---|
| Power | P | watt (W) = J s−1 |
| Current | I | ampere (A) = C s−1 |
| Potential difference | V | volt (V) = J C−1 |
The watt is a derived unit: 1 W =1 V A =1 J s−1. The product of "joules per coulomb" and "coulombs per second" is "joules per second" — pure unit cancellation makes the equation memorable.
A 12 V car headlamp draws 5.0 A. Its power dissipation is P=IV=12×5.0=60 W — enough that touching the bulb after switch-on burns your fingers. A 230 V mains kettle drawing 9.0 A dissipates P=230×9.0=2070 W ≈2.0 kW — enough to boil 0.5 L of water in about a minute.
For an ohmic resistor, V=IR (lesson 5). Substituting into P=IV gives two derived forms:
P=IV⇒P=I(IR)=I2R⇒P=V⋅RV=RV2
So:
P=IV=I2R=RV2
Mathematically equivalent for an ohmic resistor; each form is useful in different circumstances:
| Form | Use when... | Reason |
|---|---|---|
| P=IV | I and V both known | Most general; works for any device, ohmic or not |
| P=I2R | the current is fixed (e.g. transmission cable) | Quadratic in I — transmission-loss lever |
| P=V2/R | the voltage is fixed (mains-rated appliance) | Quadratic in V — domestic-rating lever |
Important. The forms P=I2R and P=V2/R only follow when V=IR holds — for an ohmic component, or for a non-ohmic component at a single operating point. For a non-ohmic component like a filament lamp, P=IV is exact at every operating point but I2R and V2/R depend on the operating-point R=V/I.
A 60 W lamp is rated for 230 V mains. Calculate (a) the operating current, (b) its operating resistance.
(a) From P=IV: I=P/V=60/230=0.261 A ≈260 mA.
(b) From P=V2/R: R=V2/P=2302/60=882 Ω.
Cross-check: R=V/I=230/0.261=881 Ω ✓; P=I2R=0.2612×882=60.1 W ✓.
A single rating "60 W at 230 V" determines both I and R at that operating point — three forms of the same law.
For constant power P over time t:
W=Pt=IVt=I2Rt=RV2t
with W in joules and t in seconds.
A 2.0 kW kettle runs on 230 V mains for 3.0 minutes.
(a) I=P/V=2000/230=8.7 A.
(b) W=Pt=2000×180=3.6×105 J =360 kJ.
Cross-check: 360 kJ is roughly the energy to raise 1 L of water by 80 K (cw=4200 J kg−1 K−1, ΔE≈336 kJ). The kettle is close to 100% efficient — all resistive heating goes into the water.
Electricity bills use the non-SI unit kWh:
1 kWh=(1000 J s−1)×(3600 s)=3.6×106 J=3.6 MJ
Memorise this. OCR examiners use both units in the same question.
2.0 kW for 3.0 minutes at 30 p/kWh.
UK average household: ∼3500 kWh/year (∼13 GJ; ∼400 W continuous average).
0.50 kWh =0.50×3.6×106=1.8×106 J.
A 230 V hair dryer rated 1200 W. UK plugs allow 3 A, 5 A, 13 A fuses.
UK rule: 3 A fuse below ∼700 W; 13 A fuse above. The fuse exists to break the circuit on a fault, not to limit normal operating current.
Joule's law P=I2R is the rate of heating in a resistor — electrons hand directed kinetic energy to the lattice via scattering, the lattice randomises it as heat. Joule's 19th-century experiments established the equivalence of mechanical, chemical and electrical heating — the foundation of the first law of thermodynamics.
Practical consequences:
A power station delivers Pdeliv=10 MW through a cable of resistance Rcable=5.0 Ω.
Case A — Naive low-voltage at VA=1000 V:
Losses are 50× the delivered power. Impossible — the cable would melt.
Case B — Grid at VB=400 kV:
Losses are 0.031% of delivered. Stepping V up 400× cuts loss by 4002=160000×, because Ploss∝I2∝1/V2 at constant delivered power.
This is the reason the UK grid runs at 132 kV, 275 kV, 400 kV — transformers step up at the station, down at the substation.
A toaster dissipates 900 W on 230 V. Element is nichrome (ρ=1.1×10−6 Ω m), diameter 0.50 mm.
Coiled into a compact ribbon. Demonstrates the interlock between lesson 7 (resistivity) and this lesson (power): given a target power and a material, you compute the length.
A car battery: 12 V, 60 Ah. Powers a 55 W headlamp.
Real lead-acid batteries deliver less than rated capacity because terminal voltage falls as chemistry depletes (lesson 9).
A filament lamp at three operating points:
| V (V) | I (A) | P=IV (W) | R=V/I (Ω) |
|---|---|---|---|
| 1.0 | 0.45 | 0.45 | 2.2 |
| 4.0 | 1.05 | 4.20 | 3.8 |
| 12.0 | 2.00 | 24.0 | 6.0 |
R rises as V rises because tungsten's positive temperature coefficient makes the filament more resistive at higher operating temperatures (∼2500 K at full brightness). At full power, P=IV=12×2.00=24 W matches the rating.
Key lesson: for non-ohmic components, P=I2R gives different answers at different operating points because R=V/I depends on the operating point. Use P=IV as the primary form.
A standard OCR PAG involves measuring the specific heat capacity of a metal block by electrical heating. A heater of resistance R=4.0 Ω is embedded in a 0.50 kg aluminium block. The heater is connected to a 12 V supply for 5.0 minutes; the block's temperature rises from 20 ∘C to 42 ∘C.
Energy supplied electrically:
Welec=RV2t=4.0122×(5.0×60)=36×300=10800 J=10.8 kJ
Heat absorbed by the block (assuming no losses):
Q=mcΔT=0.50×c×(42−20)=0.50×c×22=11c
Setting Welec=Q gives c=10800/11=980 J kg−1 K−1. Accepted value for aluminium: 897 J kg−1 K−1. The 9% discrepancy is consistent with heat losses to the surroundings during the 5-minute heating — a sensible result for an A-Level practical.
Real practicals use lagging (foam insulation) and shorter heating times to minimise losses, or apply a correction by extrapolating the cooling curve back to the heating-stop time. The basic energy bookkeeping is Welec=mcΔT+Qlosses, with the electrical input from this lesson, the thermal output from Module 5.1.
A typical UK household has the following appliances running for the stated daily durations.
| Appliance | Power | Hours/day | Daily energy (kWh) |
|---|---|---|---|
| Lighting (LED, total) | 80 W | 5 | 0.40 |
| Refrigerator | 100 W avg | 24 | 2.40 |
| Kettle | 2200 W | 0.25 | 0.55 |
| TV / electronics | 150 W | 4 | 0.60 |
| Washing machine | 800 W avg | 1 | 0.80 |
| Standby loads | 30 W | 24 | 0.72 |
| Total | 5.47 |
Subscribe to continue reading
Get full access to this lesson and all 12 lessons in this course.